| Product characteristics |
| Output signal |
switching signal; IO-Link; (configurable) |
| Measuring range |
| 0...250 bar |
0...3620 psi |
0...25 MPa |
|
| Process connection |
threaded connection G 1/4 internal thread |
| |
| Application |
| Special feature |
Gold-plated contacts |
| Measuring element |
metallic thin film cell |
| Application |
for industrial applications |
| Media |
liquids and gases |
| Medium temperature [°C] |
-25...80 |
| Min. bursting pressure |
| 1100 bar |
15950 psi |
110 MPa |
|
| Pressure rating |
|
| Vacuum resistance [mbar] |
-1000 |
| Type of pressure |
relative pressure |
| |
| Electrical data |
| Operating voltage [V] |
18...30 DC; (to SELV/PELV) |
| Current consumption [mA] |
< 35 |
| Min. insulation resistance [MΩ] |
100; (500 V DC) |
| Protection class |
III |
| Reverse polarity protection |
yes |
| Power-on delay time [s] |
< 0.3 |
| Integrated watchdog |
yes |
| |
| Inputs / outputs |
| Number of inputs and outputs |
Number of digital outputs: 2 |
| |
| Outputs |
| Total number of outputs |
2 |
| Output signal |
switching signal; IO-Link; (configurable) |
| Electrical design |
PNP/NPN |
| Number of digital outputs |
2 |
| Output function |
normally open / normally closed; (parameterisable) |
| Max. voltage drop switching output DC [V] |
2.5 |
| Permanent current rating of switching output DC [mA] |
150; (200 (...60 °C) 250 (...40 °C)) |
| Switching frequency DC [Hz] |
< 170 |
| Short-circuit protection |
yes |
| Type of short-circuit protection |
pulsed |
| Overload protection |
yes |
| |
| Measuring/setting range |
| Measuring range |
| 0...250 bar |
0...3620 psi |
0...25 MPa |
|
| |
| Factory setting / CMPT = 2 |
| Set point SP |
| 2...250 bar |
40...3620 psi |
0.2...25 MPa |
|
| Reset point rP |
| 1...249 bar |
20...3600 psi |
0.1...24.9 MPa |
|
| Min. difference between SP and rP |
|
| In steps of |
|
| |
| Status_B High Resolution / CMPT = 3 |
| Set point SP |
| 2...250 bar |
30...3626 psi |
0.2...25 MPa |
|
| Reset point rP |
| 1...249 bar |
12...3608 psi |
0.1...24.9 MPa |
|
| Min. difference between SP and rP |
|
| In steps of |
|
| |
| Accuracy / deviations |
| Switch point accuracy [% of the span] |
< ± 0,5 |
| Repeatability [% of the span] |
< ± 0,1; (with temperature fluctuations < 10 K) |
| Characteristics deviation [% of the span] |
< ± 0,25 (BFSL) / < ± 0,5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting) |
| Hysteresis deviation [% of the span] |
< ± 0,25 |
| Long-term stability [% of the span] |
< ± 0,05; (per 6 months) |
| Temperature coefficient zero point [% of the span / 10 K] |
0,2; (-25...80 °C) |
| Temperature coefficient span [% of the span / 10 K] |
0,2; (-25...80 °C) |
| |
| Response times |
| Response time [ms] |
< 3 |
| Delay time programmable dS, dr [s] |
0...50 |
| |
| Software / programming |
| Parameter setting options |
hysteresis / window; normally open / normally closed; switching logic; switch-on/switch-off delay; Damping; Display unit |
| |
| Interfaces |
| Communication interface |
IO-Link |
| Transmission type |
COM2 (38,4 kBaud) |
| IO-Link revision |
1.1 |
| SDCI standard |
IEC 61131-9 |
| SIO mode |
yes |
| Required master port type |
A; (when pin 2 not connected: B) |
| Process data analogue |
1 |
| Process data binary |
2 |
| Supported DeviceIDs |
| Type of operation |
DeviceID |
| Factory setting / CMPT = 2 |
400 |
| Status_B High Resolution / CMPT = 3 |
598 |
| PN7001 |
308 |
|
| Note |
| For further information please see the IODD PDF file under "Downloads" |
|
| |
| Factory setting / CMPT = 2 |
| Profiles |
Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis |
| Min. process cycle time [ms] |
2.3 |
| IO-Link resolution pressure [bar] |
1 |
| IO-Link resolution pressure [MPa] |
0.1 |
| IO-Link process data (cyclical) |
| function |
bit length |
| pressure |
14 |
| binary switching information |
2 |
|
| IO-Link functions (acyclical) |
application specific tag |
| |
| Status_B High Resolution / CMPT = 3 |
| Profiles |
Smart Sensor ED2: Digital Measuring Sensor (0x000A), Identification and Diagnosis (0x4000) |
| Min. process cycle time [ms] |
3 |
| IO-Link resolution pressure [bar] |
0.1 |
| IO-Link resolution pressure [MPa] |
0.02 |
| IO-Link process data (cyclical) |
| function |
bit length |
| pressure |
16 |
| device status |
4 |
| binary switching information |
2 |
|
| IO-Link functions (acyclical) |
application specific tag |
| |
| Operating conditions |
| Ambient temperature [°C] |
-25...80 |
| Storage temperature [°C] |
-40...100 |
| Protection |
IP 65; IP 67 |
| |
| Tests / approvals |
| EMC |
| DIN EN 61000-6-2 |
|
| DIN EN 61000-6-3 |
|
|
| Shock resistance |
| DIN EN 60068-2-27 |
50 g (11 ms) |
|
| Vibration resistance |
| DIN EN 60068-2-6 |
20 g (10...2000 Hz) |
|
| UL approval |
|
| Pressure Equipment Directive |
Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
| |
| Mechanical data |
| Weight [g] |
239.2 |
| Materials |
1.4542 (17-4 PH / 630); stainless steel (1.4404 / 316L); PBT+PC-GF30; PBT-GF20; PC |
| Materials (wetted parts) |
1.4542 (17-4 PH / 630) |
| Min. pressure cycles |
100 million |
| Tightening torque [Nm] |
25...35; (recommended tightening torque; depends on lubrication, seal and pressure rating) |
| Process connection |
threaded connection G 1/4 internal thread |
| Restrictor element integrated |
no (can be retrofitted) |
| |
| Displays / operating elements |
| Display |
| Display unit |
3 x LED, green (bar, psi, MPa) |
| switching status |
2 x LED, yellow |
| measured values |
alphanumeric display, red/green 4-digit |
|
| |
| Remarks |
| Pack quantity |
1 pcs. |
| |
| Electrical connection |
| Connection |